FAQs - Software - WindO/I-NV2

Software

What is the latest version of the WindO/I-NV2?

Last Updated: 2005/17/08


How can I get the Symbol Factory images?

If you purchase WindO/I-NV2 version 2.30 and above then the Symbol Factory images are included.

Last Updated: 2005/17/08


What operating systems are supported by WindO/I-NV2 software?

WindO/I-NV2 version 2.3 and above supports Windows 95 (OSR2 and later)/98/ME/NT4.0/2000/XP.

Last Updated: 2005/17/08


Can I use WindO/I-NV2 software to convert HG1B/2A program to HG2F/3F/4F?

No, the WindO/I-NV2 software can not convert the HG1B/2A program. You must recreate the whole project for HG2F/3F/4F.

Last Updated: 2005/17/08


Cable

Cable: What is the programming cable for HG2F/3F/4F?

The programming cable partnumber is HG9Z-XCM1A.

Last Updated: 2005/17/08


Where can I get the cable and communication information between the HG2F/3F/4F and PLC?

Last Updated: 2005/17/08


Where can I get commnication settings/supported addresses?

Last Updated: 2005/18/08


Hardware/Functionality

What is the brightness of HG2F/3F/4F?

HG3F/4F with 350 cd/m2 (nits) and HG2F with 250 cd/m2 (nits).

Last Updated: 2005/17/08


What size of a memory I can use with Compact Flash Card?

A CF card with memory size of 16/32/64/128/256/512 MB can be used.

Last Updated: 2005/17/08


What is the advantage of using Compact Flash Card?

It allows you to store recipe, alarm, and trend log data, multiple projects, and screen shots.

Last Updated: 2005/17/08


The Pass-Thru communication supports which PLCs?

The Pass-Thru communication allows you to download the PLC program through the HG2F/3F/4F without any interrupting to their operation. Therefore, only one cable is used to programmed the HG2F/3F/4F and the PLC. This Pass-Thru communication is available if you are using the following PLCs:

dec: Micro3, Micro3C, OpenNet, and Microsmart

Mitsubishi: Melsec-FX, FX2N, FX3UC, and Q

Last Updated: 2005/17/08


How do you enable the Pass-Thru function?

First, the WindO/I-NV2 must be version 2.7. If you have lower version, please upgrade to the latest version.

In the WindO/I-NV2 software, select Project Settings the Host I/F driver. Check the box to enable pass thru communication

Last Updated: 2005/17/08


Can I connect a single PLC with multiple HG2F/3F/4F?

Yes, a total of 16 HG2F/3F/4F can be connected with one PLC. Each touchscreen must use an O/I Link adaptor part number HG9Z-2G1. The O/I Link mode setting is done in the WindO/I-NV2 software under Project Settings/Communication Interface.

Last Updated: 2005/17/08


Can I connect a single HG2F/3F/4F with multiple PLCs?

Yes, by using the 1:N Communication mode. The maximum is 31 PLCs (may vary depending on the PLC type. Check PLC manual.)can be connected to a single HG2F/3F/4F. The following PLCs supported for the 1:N communication are:

Idec: OpenNet and Microsmart

Koyo: DirectLogic-DL205/405

Modicon: Modbus RTU

Last Updated: 2005/17/08


Class I, Div 2 Rating

What products in the HG series operator interfaces have Class1-Div2 (explosion proof) approval?

HG2F and HG1X series products have Class1-Div2 approval. HG1B and HG2A are not approved for Class1-Div2

Last Updated: 2002/08/10