Last Updated: 2005/17/08
If you purchase WindO/I-NV2 version 2.30 and above then the Symbol Factory images are included.
Last Updated: 2005/17/08
WindO/I-NV2 version 2.3 and above supports Windows 95 (OSR2 and later)/98/ME/NT4.0/2000/XP.
Last Updated: 2005/17/08
No, the WindO/I-NV2 software can not convert the HG1B/2A program. You must recreate the whole project for HG2F/3F/4F.
Last Updated: 2005/17/08
The programming cable partnumber is HG9Z-XCM1A.
Last Updated: 2005/17/08
Last Updated: 2005/17/08
Last Updated: 2005/18/08
HG3F/4F with 350 cd/m2 (nits) and HG2F with 250 cd/m2 (nits).
Last Updated: 2005/17/08
A CF card with memory size of 16/32/64/128/256/512 MB can be used.
Last Updated: 2005/17/08
It allows you to store recipe, alarm, and trend log data, multiple projects, and screen shots.
Last Updated: 2005/17/08
The Pass-Thru communication allows you to download the PLC program through the HG2F/3F/4F without any interrupting to their operation. Therefore, only one cable is used to programmed the HG2F/3F/4F and the PLC. This Pass-Thru communication is available if you are using the following PLCs:
dec: Micro3, Micro3C, OpenNet, and Microsmart
Mitsubishi: Melsec-FX, FX2N, FX3UC, and Q
Last Updated: 2005/17/08
First, the WindO/I-NV2 must be version 2.7. If you have lower version, please upgrade to the latest version.
In the WindO/I-NV2 software, select Project Settings the Host I/F driver. Check the box to enable pass thru communication
Last Updated: 2005/17/08
Yes, a total of 16 HG2F/3F/4F can be connected with one PLC. Each touchscreen must use an O/I Link adaptor part number HG9Z-2G1. The O/I Link mode setting is done in the WindO/I-NV2 software under Project Settings/Communication Interface.
Last Updated: 2005/17/08
Yes, by using the 1:N Communication mode. The maximum is 31 PLCs (may vary depending on the PLC type. Check PLC manual.)can be connected to a single HG2F/3F/4F. The following PLCs supported for the 1:N communication are:
Idec: OpenNet and Microsmart
Koyo: DirectLogic-DL205/405
Modicon: Modbus RTU
Last Updated: 2005/17/08
HG2F and HG1X series products have Class1-Div2 approval. HG1B and HG2A are not approved for Class1-Div2
Last Updated: 2002/08/10